DIXIE PIPELINE COMPANY LLC

hazardous_liquid Incident — — December 26, 2020

Incident Information

Incident DateDecember 26, 2020
OperatorDIXIE PIPELINE COMPANY LLC
CommodityHVL OR OTHER FLAMMABLE OR TOXIC FLUID WHICH IS A GAS AT AMBI
Pipeline Typehazardous_liquid

Location

State
Coordinates35.21830, -79.39180

Cause

CauseEQUIPMENT FAILURE
SubcausePUMP OR PUMP-RELATED EQUIPMENT

Casualties

Fatalities0
Injuries0

Costs

Property Damage$500
Emergency Response$0
Other Costs$0

Location Map

Incident Narrative

AT 05:40, HOUSTON CONTROL CENTER (HCC) RECEIVED A SEAL FAILURE ALARM ON UNIT NUMBER TWO AND A GAS ALARM AT THE SOUTHERN PINE PUMP STATION. HCC ISOLATED AND SHUT DOWN THE PUMP STATION, REROUTING FLOW TO THE MAINLINE. HCC CONTACTED THE OPERATIONS SUPERVISOR WHO DISPATCHING TECHNICIANS TO THE STATION. OPERATIONS ARRIVED ONSITE AND FOUND THE OUTBOARD SEAL HAD FAILED, LEAKING PRODUCT TO THE ATMOSPHERE. THE UNIT WAS BLOWN DOWN, PURGED, AND THE SEALS WERE CHANGED. VISUAL EXAMINATION OF THE FAILED SEAL INDICATES THAT EXCESSIVE HEAT LIKELY CAUSED THE SEAL FAILURE. THE EXCESSIVE HEAT IS A RESULT OF LOSS OF SEAL FLUSH, WHICH ACTS AS A COOLING AGENT FOR THE SEAL FACES. THE PUMP WAS RETURNED TO SERVICE WITH NO MECHANICAL ISSUES. PART C4 NOTE: THE SOUTHERN PINE UNIT NUMBER TWO PUMP WAS INSTALLED IN 1991, HOWEVER, THE SEAL WAS REPLACED IN 2017.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.