MAGELLAN PIPELINE COMPANY, LP

hazardous_liquid Incident —

Incident Information

Report Date
OperatorMAGELLAN PIPELINE COMPANY, LP
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates35.30897, -94.39304

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

AT 18:11 ON DECEMBER 30, THE MAGELLAN OPERATIONS CONTROL RECEIVED A CALL FROM A 3RD PARTY REPORTING THE SMELL OF GASOLINE NEAR THE FT SMITH FACILITY. ALL PIPELINE AND FACILITY MOVEMENTS WERE SHUT DOWN AND AN INVESTIGATION EVENT WAS INITIATED. AT 18:36, THE FT SMITH FIRE DEPARTMENT IDENTIFIED THE SOURCE OF THE GASOLINE AS MAGELLAN'S FT SMITH FACILITY. MAGELLAN PERSONNEL ARRIVED ON SITE AND CLEANUP ACTIVITIES WERE INITIATED. THE SOURCE OF THE RELEASE WAS DISCOVERED TO BE CRACKED TUBING ON THE MAINLINE UNIT. METALLURGICAL ANALYSIS CONFIRMED THAT MINIMAL TUBING SUPPORT AND TYPICAL PUMP VIBRATION LED TO FATIGUE CRACKING OF THE TUBING. THE CRACKED TUBING WAS REPLACED WITH 0.065"" WT TUBING AND ADDITIONAL SUPPORTS WERE ADDED. SUPPLEMENTAL/FINAL (03/22/2021): UPDATED PARTS A-18A, G6-6, PART H

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.