"ONEOK NGL PIPELINE, LLC"

hazardous_liquid Incident — — November 2, 2022

Incident Information

Incident DateNovember 2, 2022
Operator"ONEOK NGL PIPELINE, LLC"
CommodityHVL OR OTHER FLAMMABLE OR TOXIC FLUID WHICH IS A GAS AT AMBI
Pipeline Typehazardous_liquid

Location

State
Coordinates29.85469, -94.89248

Cause

CauseEQUIPMENT FAILURE
SubcauseTHREADED CONNECTION/COUPLING FAILURE

Casualties

Fatalities0
Injuries0

Costs

Property Damage$500
Emergency Response$400
Other Costs$0

Location Map

Incident Narrative

"ON 11-2-22 AT APPROXIMATELY 8:58AM, ONEOK PERSONNEL IDENTIFIED A LEAK NEAR PUMP 122 AT THE ONEOK MONT BELVIEU PUMP STATION. EMERGENCY RESPONSE MEASURES WERE INITIATED AND THE LOCATION OF THE LEAK WAS ISOLATED. A 1"" THREADED NIPPLE ON THE SUCTION VALVE THERMAL BYPASS WAS FOUND TO HAVE A CRACK CAUSING THE RELEASE. THE 1"" THREADED NIPPLE HAS BEEN SENT FOR MATERIAL ANALYSIS. A SUPPLEMENTAL REPORT WILL BE SUBMITTED WHEN THE MATERIAL ANALYSIS RESULTS ARE RECEIVED AND ONEOK'S INVESTIGATION INTO THE FAILURE IS COMPLETED. UPDATE 1/5/23 SUPPLEMENTAL/FINAL THE FAILED 1"" THREADED NIPPLE HAS BEEN REPLACED WITH A 1"" WELDOLET AND THE 1"" SUCTION VALVE THERMAL BYPASS PIPING HAS BEEN REINFORCED WITH SUPPORTS. NO MATERIAL ANALYSIS RESULTS ARE AVAILABLE DUE TO THE FAILED 1"" THREADED NIPPLE BEING FURTHER DAMAGED DURING REMOVAL."