ENTERPRISE CRUDE PIPELINE LLC

hazardous_liquid Incident —

Incident Information

Report Date
OperatorENTERPRISE CRUDE PIPELINE LLC
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates29.82619, -94.88545

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

ON 2/19/2021 AT APPROXIMATELY 14:01 CST, A PIPELINE TECHNICIAN AT FINNEGAN PUMP STATION DISCOVERED OIL SPILLING FROM TUBING THAT HAD SEPARATED FROM A CHECK VALVE. THE CHECK VALVE WAS ATTACHED BY A FERRULE NUT ON THE DISCHARGE TUBING OF A CHEMICAL INJECTION PUMP. IN RESPONSE, PIPELINE TECH ISOLATED THE SECTION OF TUBING. UPON INVESTIGATION, IT WAS DETERMINED THAT THE CHECK VALVE FAILED FIRST, WHICH THEN CAUSED THE CHEMICAL INJECTION PUMP FITTING TO PRESSURIZE AND DETACH FROM THE TUBING. FAILED CHECK VALVE AND TUBING HAS BEEN REPLACED. TWO BBLS HIT THE GROUND WITH NO IMPACT TO WATER. SITE REMEDIATION IS COMPLETE.