MAGELLAN PIPELINE COMPANY, LP

hazardous_liquid Incident —

Incident Information

Report Date
OperatorMAGELLAN PIPELINE COMPANY, LP
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates30.35086, -95.89931

Cause

CauseNATURAL FORCE DAMAGE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

AT 10:00 ON FEBRUARY 20, 2021, MAGELLAN OPERATIONS PERSONNEL WERE PERFORMING AN INSPECTION OF THE PLANTERSVILLE PUMP STATION DUE TO RECENT ICE STORMS WHEN A LEAK WAS DISCOVERED ON A 2"" BALL VALVE BELOW THE STRAINER. THE STRAINER WAS ISOLATED AND CLEANUP ACTIVITIES WERE INITIATED. THE VALVE CRACKED DUE TO WATER FREEZING IN THE VALVE BODY. THE CRACKED VALVE WAS REPLACED WITH A NEW 2"" BALL VALVE. MODIFICATIONS WERE MADE TO THE SITE SPECIFIC WINTERIZATION PROCEDURE TO INCLUDE THIS LOW POINT.