WINK TO WEBSTER PIPELINE, LLC

hazardous_liquid Incident —

Incident Information

Report Date
OperatorWINK TO WEBSTER PIPELINE, LLC
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates29.61211, -95.18608

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

ON THE MORNING OF FRIDAY, JUNE 10, EXXONMOBIL PIPELINE CO. (EMPCO) WAS NOTIFIED BY A THIRD PARTY OPERATOR OF A SPILL AT THE WINK TO WEBSTER ECHO STATION AT 0709. UPON NOTICE, EMPCO SHUT DOWN AND ISOLATED THE STATION AT 0712. EMPCO PERSONNEL ARRIVED ONSITE AT 7:45 AND CONFIRMED A REPORTABLE VOLUME AT 0750. THE SOURCE OF THE SPILL WAS ISOLATED, MITIGATED AND THE SITE WAS CLEANED UP. THE CAUSE WAS DETERMINED TO BE A 3/4 INCH MANIFOLD VALVE CONNECTED TO A PRESSURE GAUGE THAT EXPERIENCED EXCESSIVE VIBRATION DURING START UP OF THE FACILITY. A BLEEDER VALVE ON THE MANIFOLD VALVE LOOSENED AS A RESULT OF THE VIBRATION WHICH RESULTED IN THE SPILL. THE PRESSURE GAUGE AND ASSOCIATED VALVE WAS REMOVED AND PLUGGED. EMPCO IDENTIFIED OTHER LOCATIONS WHERE SIMILAR VALVES ARE INSTALLED AND EMPCO IS REPLACING OR PLUGGING THE SIMILAR MANIFOLD VALVES. (PLEASE NOTE: EXXONMOBIL PIPELINE COMPANY IS THE CONTRACTUAL SERVICE PROVIDER FOR WINK TO WEBSTER PIPELINE, LLC)