DELEK MARKETING AND SUPPLY, LP

hazardous_liquid Incident — — July 19, 2021

Incident Information

Incident DateJuly 19, 2021
OperatorDELEK MARKETING AND SUPPLY, LP
CommodityREFINED AND/OR PETROLEUM PRODUCT (NON-HVL) WHICH IS A LIQUID
Pipeline Typehazardous_liquid

Location

State
Coordinates32.54293, -99.76563

Cause

CauseEQUIPMENT FAILURE
SubcausePUMP OR PUMP-RELATED EQUIPMENT

Casualties

Fatalities0
Injuries0

Costs

Property Damage$28,850
Emergency Response$3,000
Other Costs$0

Location Map

Incident Narrative

LOCAL OPERATING PERSONNEL IDENTIFIED RELEASE FROM FAILED PUMP SEAL ON VERTICAL PUMP. OPERATING PERSONNEL CONTACTED THE CONTROL CENTER, WHO SHUT THE PIPELINE DOWN. THE RELEASE WAS CONFINED TO CONCRETE PUMP CONTAINMENT. THE SOURCE OF THE RELEASE WAS A FAILED PACKING. WEAR ON THE PUMP SHAFT BUSHINGS WAS FOUND WHICH ALLOWED THE PACKING TO PREMATURELY WEAR.