ENTERPRISE PRODUCTS OPERATING LLC
hazardous_liquid Incident —
Incident Information
| Report Date | — |
| Operator | ENTERPRISE PRODUCTS OPERATING LLC |
| Commodity | — |
| Pipeline Type | hazardous_liquid |
Location
| State | |
| Coordinates | 29.68151, -95.01540 |
Cause
| Cause | INCORRECT OPERATION |
| Subcause | — |
Casualties
| Fatalities | 0 |
| Injuries | 0 |
Costs
| Property Damage | — |
| Lost Commodity | — |
| Public/Private Damage | — |
| Emergency Response | — |
| Environmental Remediation | — |
| Other Costs | — |
Location Map
Incident Narrative
ON 7/31/21, AT 12:40 PM, GAS DETECTORS ALARMED AT THE MORGAN'S POINT FACILITY AND LOCAL PERSONNEL OBSERVED TANK 163 PSVS RELIEVING TO ATMOSPHERE. PL CONTROL WAS NOTIFIED TO SHUT DOWN INCOMING FLOW TO THE TANK AND RE-OPEN THE CONTROL VALVE TO THE FLARE SYSTEM. THE TANK WAS DEPRESSURIZED AND EQUIPMENT INSPECTED. AN INVESTIGATION DETERMINED THAT THE CONTROLLER PLACED A CONTROL VALVE IN MANUAL MODE TO MANUALLY CONTROL THE FLARE SYSTEM PRESSURE. ONCE THE CONTROL VALVE WAS PLACED IN MANUAL MODE AND CLOSED, THE SYSTEM PRESSURE INCREASED AND THE CONTROLLER DID NOT REACT IN TIME TO RELIEVE THE SYSTEM PRESSURE. THE RRC WAS NOTIFIED ON 8/2/2021 AT 14:51, INCIDENT #2460