ENTERPRISE PRODUCTS OPERATING LLC

hazardous_liquid Incident —

Incident Information

Report Date
OperatorENTERPRISE PRODUCTS OPERATING LLC
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates35.84816, -101.43227

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

ON 08/17/21 ENTERPRISE TECHNICIANS WERE COMPLETING MAINTENANCE WORK ON PUMP #1 AT STINNETT STATION. WHILE PREPARING THE PUMP FOR SERVICE, A 1/2"" TUBING LINE DETACHED FROM ITS COMPRESSION FITTING AND RELEASED Y-GRADE INTO THE ATMOSPHERE. THE UNIT WAS ISOLATED AND CONNECTED TO FLARE TO RELIEVE REMAINING PRESSURE. THE STATION WAS ALREADY SHUT DOWN WHEN THE INCIDENT OCCURRED. UPON EXAMINATION THE THREADS OF THE FITTING WERE FOUND DAMAGED SUGGESTING THAT A CROSS THREADED PRESSURE WAS APPLIED TO THE NUT AND FERRULE, WHICH CAUSED THE TUBING TO SLIP FROM THE FERRULE. TECHNICIANS RECEIVED MANUFACTURER SPECIFIC TRAINING MATERIAL ON TUBE FITTING ASSEMBLY.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in