ENTERPRISE PRODUCTS OPERATING LLC

hazardous_liquid Incident —

Incident Information

Report Date
OperatorENTERPRISE PRODUCTS OPERATING LLC
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates35.57208, -101.12427

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

ON 12/09/21 AT 06:50 CST, AN ENTERPRISE TECHNICIAN NOTICED PRODUCT RELEASING INTO THE ATMOSPHERE BY THE SOUTH RED METER RUN AT SKELLYTOWN STATION. PIPELINE CONTROL WAS IMMEDIATELY NOTIFIED AND THE PIPELINE WAS SHUTDOWN. UPON INVESTIGATION A NIPPLE CONNECTION LEADING TO TWO TRANSMITTERS HAD CRACKED AND RELEASED APPROXIMATELY 7 BARRELS OF NORMAL BUTANE INTO THE ATMOSPHERE. THE CAUSE OF THE FAILURE WAS DETERMINED TO BE UNSUPPORTED WEIGHT ON A SMALL DIAMETER NIPPLE COUPLED WITH VIBRATION FROM NORMAL OPERATIONS. A SUPPORT RACK WAS BUILT TO BEAR THE WEIGHT OF THE TRANSMITTERS AND THE BROKEN NIPPLE WAS REPLACED.