BUCKEYE PARTNERS, LP

hazardous_liquid Incident —

Incident Information

Report Date
OperatorBUCKEYE PARTNERS, LP
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates39.12201, -94.43841

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

TANK WATER DRAW VALVE DID NOT PROPERLY SEAL WHICH CAUSED ICE TO FORM IN THE INTERSTITIAL SPACE IN BETWEEN THE INNER AND OUTER VALVE OF THE VALVE RESULTING IN THE RELEASE. UPDATE FOR CLOSURE 5-12-2022: AFTER REMOVAL OF THE VALVE THERE WAS DEBRIS DISCOVERED IN THE INTERSTITIAL SPACE OF THE VALVE WHICH PREVENTED IT FROM PROPERLY SEATING. A NEW WATER DRAW DRAIN VALVE HAS BEEN INSTALLED AND IS OPERATING NORMALLY.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in