ROSE ROCK MIDSTREAM OPERATING, LLC

hazardous_liquid Incident — — February 12, 2022

Incident Information

Incident DateFebruary 12, 2022
OperatorROSE ROCK MIDSTREAM OPERATING, LLC
CommodityCRUDE OIL
Pipeline Typehazardous_liquid

Location

State
Coordinates36.01140, -96.74700

Cause

CauseEQUIPMENT FAILURE
SubcauseNON-THREADED CONNECTION FAILURE

Casualties

Fatalities0
Injuries0

Costs

Property Damage$300,000
Emergency Response$65,000
Other Costs$0

Location Map

Incident Narrative

ON SATURDAY FEBRUARY 12TH AT 05:45, A PIPELINE TECHNICIAN PERFORMING ROUTINE STATION CHECK NOTICED A STRONG SMELL OF CRUDE OIL NEAR TANK 3501. THE TECHNICIAN IMMEDIATELY INVESTIGATED AND NOTICED A CRUDE OIL AND WATER MIX FLOWING FROM THE ROOF DRAIN. THE TECHNICIAN IMMEDIATELY CLOSED THE ROOF DRAIN VALVE WHICH STOPPED THE FLOW OF OIL AND WATER MIXTURE. THE ENTIRE RELEASE WAS CONTAINED TO THE DIKE AREA. THE TECHNICIAN MADE APPROPRIATE NOTIFICATIONS AND INITIATED REMEDIAL ACTIVITIES. ALL FREE PRODUCT WAS COLLECTED, DECANTED AND RETURNED TO TANKAGE; THE DIKE AREA SOIL WAS COLLECTED AND IS BEING REMEDIATED. CLEAN FILL WAS BROUGHT IN. FOLLOWING RELEASE CONTAINMENT AND REMEDIAL ACTIVITIES THE REMAINING PRODUCT IN TANK 3501 WAS PUMPED TO ANOTHER TANK SO TANK 3501 COULD BE FULLY ISOLATED AND AN INVESTIGATION INTO THE CAUSE CAN BE PERFORMED. THE CAUSE OF THE ROOF DRAIN FAILURE WAS ATTRIBUTED TO A PAPER GASKET FAILURE IN THE FLANGED CONNECTION OF THE ROOF DRAIN SYSTEM. THE INVESTIGATION OF THE INCIDENT CONCLUDED THAT A LUBRICANT APPLIED DIRECTLY TO THE PAPER GASKET CAUSED DETERIORATION OVER TIME AND THUS CAUSE THE LEAK. A CHANGE TO FLEX METALLIC GASKET WAS MADE TO PREVENT THIS TYPE OF FAILURE FROM OCCURRING AGAIN.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in