KINDER MORGAN LIQUID TERMINALS, LLC

hazardous_liquid Incident —

Incident Information

Report Date
OperatorKINDER MORGAN LIQUID TERMINALS, LLC
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates40.52179, -74.25288

Cause

CauseINCORRECT OPERATION
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

TANK 60 LEAK FOUND COMING FROM 10 O'CLOCK POSITION ON MANWAY. DROP PAN WAS PLACED UNDER THE MANWAY AND BOLTS WERE TIGHTENED. LEAK DID NOT STOP. PRODUCT WAS TRANSFERRED TO ANOTHER TANK AND MANWAY WAS REMOVED AND FACE INSPECTED. MANWAY WAS FOUND NOT TO BE FLUSH AND APPROXIMATELY 1/8"" FROM FLUSH AT THE 5 O'CLOCK POSITION. NEW GASKET PUT ON AND MANWAY COVER REPLACED AND SECURED. INVESTIGATION DETERMINED THAT THE CONTRACTOR FAILED TO TORQUE THE MANWAY BOLTS PER OUR PROCEDURE. CONTRACTOR EMPLOYEE TO BE RETRAINED AND REQUALIFIED IN THE SPECIFIC OQ TASK.