ULTRAMAR INC.

hazardous_liquid Incident —

Incident Information

Report Date
OperatorULTRAMAR INC.
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates33.77667, -118.23257

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

ON 9/14/2022, AROUND 1820 THE OPERATOR TRIED TO START BLEND A1-270 TO SHELL BUT ONE OF THE PUMPS (82-P-21A) DID NOT START AND BOTH A AND B PUMPS WERE NEEDED FOR THE BLEND. THE OPERATOR CHECKED THE BREAKER AT SUBSTATION 5 BUT IT DIDN'T HAVE ANY ALARMS, BUT RESET THE PUMP ANYWAYS. AT 1857 THE BLEND WAS ATTEMPTED AGAIN AND BOTH PUMPS (82-P-21 A&B) STARTED NORMALLY. THE OPERATOR NOTICED A HIGH DIFFERENTIAL PRESSURE ON THE PRESSURE INDICATION (82-PHS-851C) AND PROCEEDED TO OPEN UP THE SECOND SET OF FILTERS (82PHS851A). WHEN THE OPERATOR WENT TO THE FIELD TO VERIFY THAT THE VALVES OPENED, HE NOTICED THAT THE FILTER HOUSING HAD BROKEN OFF AND GASOLINE WAS COMING OUT. THE BLEND WAS IMMEDIATELY SHUTDOWN TO STOP THE LEAK. THE BLEND WAS RESTARTED WITH (82-PSH-851C) SECONDARY FILTERS ONLINE, AND FAILED FILTERS (82PSH851A) CLOSED, WITH NO DIFFERENTIAL PRESSURE ISSUES. 0.43 BARRELS OF GASOLINE LEAKED TO SOIL AND CONCRETE, ALL CONTAINED WITHIN THE REFINERY. A WORK REQUEST WAS PUT IN TO REPLACE THE FILTER/HOUSING AND TO COMPLETE SOIL REMEDIATION. SOIL REMEDIATION REPLACED 3 CUBIC FEET OF SOIL AND WAS COMPLETED 9/15/22. SHIFT SUPERVISOR, SHIFT SUPERINTENDENT, AREA SUPERINTENDENT AND ENVIRONMENTAL WERE NOTIFIED.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in