ONEOK NGL PIPELINE, LLC
hazardous_liquid Incident —
Incident Information
| Report Date | — |
| Operator | ONEOK NGL PIPELINE, LLC |
| Commodity | — |
| Pipeline Type | hazardous_liquid |
Location
| State | |
| Coordinates | 29.85469, -94.89248 |
Cause
| Cause | EQUIPMENT FAILURE |
| Subcause | — |
Casualties
| Fatalities | 0 |
| Injuries | 0 |
Costs
| Property Damage | — |
| Lost Commodity | — |
| Public/Private Damage | — |
| Emergency Response | — |
| Environmental Remediation | — |
| Other Costs | — |
Location Map
Incident Narrative
ON 11-2-22 AT APPROXIMATELY 8:58AM, ONEOK PERSONNEL IDENTIFIED A LEAK NEAR PUMP 122 AT THE ONEOK MONT BELVIEU PUMP STATION. EMERGENCY RESPONSE MEASURES WERE INITIATED AND THE LOCATION OF THE LEAK WAS ISOLATED. A 1"" THREADED NIPPLE ON THE SUCTION VALVE THERMAL BYPASS WAS FOUND TO HAVE A CRACK CAUSING THE RELEASE. THE 1"" THREADED NIPPLE HAS BEEN SENT FOR MATERIAL ANALYSIS. A SUPPLEMENTAL REPORT WILL BE SUBMITTED WHEN THE MATERIAL ANALYSIS RESULTS ARE RECEIVED AND ONEOK'S INVESTIGATION INTO THE FAILURE IS COMPLETED. UPDATE 1/5/23 SUPPLEMENTAL/FINAL THE FAILED 1"" THREADED NIPPLE HAS BEEN REPLACED WITH A 1"" WELDOLET AND THE 1"" SUCTION VALVE THERMAL BYPASS PIPING HAS BEEN REINFORCED WITH SUPPORTS. NO MATERIAL ANALYSIS RESULTS ARE AVAILABLE DUE TO THE FAILED 1"" THREADED NIPPLE BEING FURTHER DAMAGED DURING REMOVAL.
About This Pipeline Incident
Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.