"NUSTAR LOGISTICS, L.P."

hazardous_liquid Incident — — October 3, 2024

Incident Information

Incident DateOctober 3, 2024
Operator"NUSTAR LOGISTICS, L.P."
CommodityCRUDE OIL
Pipeline Typehazardous_liquid

Location

State
Coordinates28.63158, -98.79009

Cause

CauseCORROSION FAILURE
SubcauseINTERNAL CORROSION

Casualties

Fatalities0
Injuries0

Costs

Property Damage$12,217
Emergency Response$2,538
Other Costs$0

Location Map

Incident Narrative

"WHILE PERFORMING A ROUTINE MAINTENANCE INSPECTION, COMPANY OPERATIONS PERSONNEL DISCOVERED A CRUDE OIL LEAK INSIDE NUSTAR'S HWY 97 TERMINAL TANK FARM. THE LEAK ORIGINATED AT THE 6 O'CLOCK POSITION OF A STRAINER/FILTER VESSEL LOCATED UPSTREAM OF BOOSTER PUMP 404 AND WITHIN TANK 403'S CONTAINMENT. NUSTAR'S 70P CHOKE CANYON PIPELINE SYSTEM WAS SHUT DOWN, AND BOTH SUCTION AND DISCHARGE VALVES WERE USED TO ISOLATE THE BOOSTER PUMP STATION. UPDATE - THE LEAK OCCURRED ON THE BOTTOM HEAD OF THE STRAINER AT A THROUGH-WALL INTERNAL CORROSION PIT. THE CAUSE OF THE LEAK IS INTERNAL CORROSION OF THE COMPONENT SURFACE DUE TO MICROBIOLOGICALLY INFLUENCED CORROSION."

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in