COPANO NGL SERVICES LLC

hazardous_liquid Incident — — November 11, 2024

Incident Information

Incident DateNovember 11, 2024
OperatorCOPANO NGL SERVICES LLC
CommodityHVL OR OTHER FLAMMABLE OR TOXIC FLUID WHICH IS A GAS AT AMBI
Pipeline Typehazardous_liquid

Location

State
Coordinates29.69337, -96.64262

Cause

CauseEQUIPMENT FAILURE
SubcauseNON-THREADED CONNECTION FAILURE

Casualties

Fatalities0
Injuries0

Costs

Property Damage$203,000
Emergency Response$0
Other Costs$0

Location Map

Incident Narrative

"ON NOVEMBER 11, 2024, COPANO FIELD PERSONNEL DISCOVERED A SMALL PATCH OF ICE AT MLV-1 AND HEARD A ""LEAKING"" SOUND WHILE COMPLETING ROUTINE VALVE MAINTENANCE. THE ""COP6-BRENHAM"" LINE WAS PROMPTLY ISOLATED AND THE REMAINING PRODUCT IN THE LINE WAS FLARED TO START REPAIRS. A FATIGUED FLANGE GASKET ON AN UNDERGROUND VALVE WAS DETERMINED TO BE THE CAUSE OF THE LEAK AT MLV-1. REPAIRS INCLUDED INSTALLING A NEW SPIRAL WOUND 304 STAINLESS GASKET ON MLV-1. THE NGL LINE WAS RETURNED TO SERVICE ON NOVEMBER 22, 2024."

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in