ENERGY TRANSFER NEDERLAND TERMINAL LLC

hazardous_liquid Incident —

Incident Information

Report Date
OperatorENERGY TRANSFER NEDERLAND TERMINAL LLC
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates29.99831, -93.99013

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

ON 6/28/2023 AT APPROXIMATELY 07:50, THE DUTY FOREMAN RECEIVED A CALL THAT THE FRONT SUMP AT CENTRAL MANIFOLD WAS OVERFLOWING. LOCAL OPERATIONS PERSONNEL RESPONDED TO THE CENTRAL MANIFOLD AND STOPPED ALL TRANSFERS TO DETERMINE WHICH LINE THE OIL WAS COMING FROM. APPROXIMATELY, 20 GALLONS OF CRUDE OIL RELEASED INTO THE SUMP CONTAINMENT AREA. CLEAN-UP CONTRACTORS WERE DISPATCHED TO THE AREA TO COLLECT THE FREE PRODUCT. INVESTIGATION DETERMINED THAT 4-INCH DRAIN VALVE WAS LEAKING BY AND BYPASSING CRUDE OIL INTO THE SUMP CAUSING IT TO OVERFILL INTO THE CONTAINMENT. FURTHER INVESTIGATION IN THE LOCAL CONTROL ROOM IDENTIFIED THAT THE SCADA HI SUMP ALARM WAS NOT LOCATED ON THE ACTIVE SCREEN WHEN CONTROLLING THE CENTRAL MANIFOLD. THE ALARM WAS MOVED TO BE VISIBLE ON THE ACTIVE SCREEN TO PREVENT RECURRENCE. A NEW DRAIN VALVE WAS INSTALLED, AND A VAPOR BLIND WAS INSTALLED TO BLOCK THE OIL COMING FROM THE 26-INCH LINE.