EXPLORER PIPELINE CO

hazardous_liquid Incident —

Incident Information

Report Date
OperatorEXPLORER PIPELINE CO
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates39.70737, -89.17723

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

ON AUGUST 6, 2023, THE DECATUR, IL PUMP STATION RECEIVED A PUMP SEAL FAIL ALARM FROM A LARGE RAINFALL EVENT. THE SEAL FAIL ALARM ISOLATED THE PUMP, WHICH WAS NOT OPERATING SINCE THE STATION WAS DOWN. THE CONTROLLER ADDITIONALLY ISOLATED THE STATION FROM THE MAINLINE PIPELINE, SHUT DOWN THE PIPELINE, AND INITIATED A STATION CALL OUT. UPON THE TECHNICIANS ARRIVAL AT THE STATION, THE TECHNICIAN DISCOVERED 130 GALLONS OF NATURAL GASOLINE HAD BEEN RELEASED FROM THE SUCTION VALVE OF THE PUMP. ALL THE PRODUCT THAT WAS RELEASED WAS TOTALLY CONTAINED IN THE VALVE VAULT INSIDE A SECURED STATION. THE PRODUCT IN THE VAULT WAS PROPERLY MANAGED BY A CONTRACTED OSRO. THE RELEASE WAS CAUSED BY VALVE STEM WEAR ON THE PACKING WHEN IT WAS SHUT. THE PIPELINE REMAINED SHUT DOWN UNTIL THE VALVE WAS REPAIRED. SCADA RECORDS SHOW NO ADDITIONAL ALARMS OTHER THAN THE ORIGINAL SEAL FAIL, WHICH WAS CAUSED FROM A STORM AND RAINFALL THAT HAD BEEN ABLE TO SEEP INTO THE SEAL POT.