ENERGY TRANSFER COMPANY

hazardous_liquid Incident —

Incident Information

Report Date
OperatorENERGY TRANSFER COMPANY
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates32.06756, -96.47884

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

ON 12/01/2023 AT 15:00, A LOCAL OPERATOR WAS PERFORMING A ROUTINE MONTHLY TANK INSPECTION ON TANK 2725 AT THE CORSICANA TANK FARM AND OBSERVED A SMALL OIL RESIDUE AROUND THE ROOF DRAIN DISCHARGE VALVE AND PRODUCT ON THE GROUND WHERE THE DRAIN VALVE DISCHARGES FROM THE TANK. APPROXIMATELY, 30 GALLONS OF CRUDE OIL WAS RELEASED ON THE GROUND. FREE PRODUCT WAS RECOVERED WITH A VACUUM TRUCK. CONTAMINATED SOIL WAS REMOVED FOR ONSITE REMEDIATION. SUPPLEMENTAL: THE FAILURE WAS DETERMINED TO HAVE BEEN CAUSED BY A FAILURE OF THE EXTERNAL FLOATING ROOF TANK DRAIN HOSE WHICH IS UTILIZED TO DRAIN WATER FROM THE ROOF. THE HOSE IS COMPRISED OF AN EXTERNAL THERMOPLASTIC SHEATH EXTRUDED OVER A SPIRAL WOUND STAINLESS STEEL INTERNAL CARCASS. THE ANALYSIS DETERMINED THE HOSE HAD EXPERIENCED MECHANICAL DAMAGE SUSPECTED TO HAVE OCCURRED DUE TO A MISSING GUARD ON A TANK LEG. THE CONTACT ABRADED THE EXTERNAL SURFACE, AND EVENTUALLY PUNCTURED THE THERMOPLASTIC SHEATH. THE HOSE HAS BEEN REPLACED WITH A NEW DESIGN AND THE TANK LEG GUARDS HAVE BEEN INSPECTED TO PREVENT REOCCURRENCE

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in