CENTURION PIPELINE L.P.

hazardous_liquid Incident —

Incident Information

Report Date
OperatorCENTURION PIPELINE L.P.
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates34.41109, -100.28264

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

ON DECEMBER 9, 2023 AT 9:12 AM, THERE WAS A POWER FAILURE AND LOSS OF COMMUNICATIONS TO THE PLC AT CPL'S CHILDRESS STATION LOCATED NEAR CHILDRESS, TEXAS IN CHILDRESS COUNTY, TEXAS. CONTROL CENTER NOTIFIED A FIELD EMPLOYEE AT 09:15AM TO DISPATCH TO CHILDRESS STATION. AT 09:30AM, THE EMPLOYEE ARRIVED ON-SITE AND DISCOVERED A LEAK LOCATED NEAR THE SUMP INSIDE CHILDRESS STATION. CONTROL CENTER SHUT DOWN FLOW INTO CHILDRESS STATION. SEVEN (7) BARRELS OF CRUDE OIL WERE RELEASED AND CONTAINED COMPLETELY ON-SITE. THE CONTAMINATED SOIL WILL BE REMEDIATED ON-SITE. NO INJURIES, FATALITIES OR FIRES WERE ASSOCIATED WITH THIS INCIDENT. A NOTIFICATION TO THE NATIONAL RESPONSE CENTER (NRC) WAS NOT REQUIRED. AT THE TIME OF THIS WRITING, REPAIRS ARE COMPLETE AND THE INVESTIGATION STILL ONGOING AND THE RESULTING INFORMATION SUBMITTED VIA SUPPLEMENTAL REPORT(S). SUPPLEMENTAL REPORT FILED ON MARCH 12, 2024: DURING THE ROOT CAUSE ANALYSIS, IT WAS DETERMINED TO BE EQUIPMENT FAILURE DUE TO LOSS OF COMMUNICATION FROM A POWER OUTAGE. THE BATTERY BACKUP FAILED AND THERE WAS NOT A GENERATOR INSTALLED ON-SITE. THE BATTERIES WAS REPLACED AND A GENERATOR WAS INSTALLED TO PREVENT REOCCURRENCE IN THE FUTURE.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in