COLONIAL PIPELINE CO

hazardous_liquid Incident —

Incident Information

Report Date
OperatorCOLONIAL PIPELINE CO
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates33.42126, -86.28645

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

ON JANUARY 8, 2024, AT 12:17 LOCAL TIME, A COLONIAL EMPLOYEE WAS PERFORMING A ROUTINE STATION CHECK AT THE ST. IVES BOOSTER STATION IN ALPINE, ALABAMA. THE EMPLOYEE OBSERVED PRODUCT STAINING ON THE GROUND AROUND THE LINE 2 UNIT 3 PUMP INSIDE THE FACILITY. UPON FURTHER INVESTIGATION, THE EMPLOYEE IDENTIFIED AN ACTIVE LEAK FROM A PINHOLE IN TUBING ASSOCIATED WITH THE UNIT. AN INCIDENT ANALYSIS DETERMINED THAT THE CAUSE OF THE LEAK WAS EQUIPMENT FAILURE. THE 1/2-INCH DIAMETER STAINLESS STEEL TUBING REMAINED IN CONTACT WITH A STEEL SUPPORT FOR AN INDETERMINATE PERIOD OF TIME CAUSING A WEAR GROOVE IN THE SUPPORT RESULTING IN A PINHOLE LEAK IN THE TUBING.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.