MAGELLAN PIPELINE COMPANY, LP

hazardous_liquid Incident —

Incident Information

Report Date
OperatorMAGELLAN PIPELINE COMPANY, LP
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates45.10933, -95.08181

Cause

CauseNATURAL FORCE DAMAGE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

AT 13:53 ON JANUARY 26TH, 2024 OPERATIONS PERSONNEL CONDUCTING DAILY FACILITY INSPECTIONS AT WILLMAR STATION FOUND PRODUCT RELEASED FROM THE DRAIN LINE TO THE SUMP. THE AFFECTED LOCATION WAS ISOLATED AND CLEANUP ACTIVITIES WERE INITIATED. FURTHER INVESTIGATION DETERMINED A THREADED UNION ON THE DRAIN LINE CRACKED AS A RESULT OF SUSTAINED FREEZING TEMPERATURES CAUSING FROST HEAVE TO PUSH THE CONCRETE CURB UNDER THE DRAIN LINE UP INTO THE UNION, EXERTING A FORCE THAT CAUSED THE FAILURE. TO PREVENT A REOCCURRENCE, THE CURBING WAS REMOVED, DRAIN LINE WAS REPAIRED, AND THE UNION WAS REPLACED.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in