CENTERPOINT ENERGY GAS TRANSMISSION

gas_transmission Incident — — July 14, 2012

Incident Information

Incident DateJuly 14, 2012
OperatorCENTERPOINT ENERGY GAS TRANSMISSION
CommodityNATURAL GAS
Pipeline Typegas_transmission

Location

State
Coordinates34.43104, -94.44921

Cause

CauseINCORRECT OPERATION
SubcauseVALVE LEFT OR PLACED IN WRONG POSITION, BUT NOT RESULTING IN AN OVERPRESSURE

Casualties

Fatalities0
Injuries0

Costs

Property Damage$0
Emergency Response$900
Other Costs$0

Location Map

Incident Narrative

CEGT COVE COMPRESSOR - ON 7/14/2012, AT APPROXIMATELY 9:34AM, A PRESSURE BLEED-OFF TRIGGERED AN UN-INTENDED EMERGENCY SHUT-DOWN (ESD) AT THE COMPRESSOR STATION. A CEGT TECHNICIAN FAILED TO RETURN ALL VALVES TO THEIR FOUND POSITION UPON COMPLETION OF THE WORK TASK RESULTING IN ACTIVATION OF THE COMPRESSOR ESD SYSTEM. UPON ACTIVATION OF THE COMPRESSOR ESD SYSTEM BOTH THE SUCTION AND DISCHARGE ESD VALVES FAILED TO CLOSE. AN INCIDENT INVESTIGATION FOUND THAT DEBRIS PRESENT IN THE VALVES CAUSED THEM TO BIND OR SEIZE EFFECTIVELY DISABLING OPERATION OF THE VALVES.