TRANSWESTERN PIPELINE COMPANY LLC

gas_transmission Incident — — February 22, 2015

Incident Information

Incident DateFebruary 22, 2015
OperatorTRANSWESTERN PIPELINE COMPANY LLC
CommodityNATURAL GAS
Pipeline Typegas_transmission

Location

State
Coordinates33.91906, -105.32637

Cause

CauseEQUIPMENT FAILURE
SubcauseMALFUNCTION OF CONTROL/RELIEF EQUIPMENT

Casualties

Fatalities0
Injuries0

Costs

Property Damage$0
Emergency Response$0
Other Costs$0

Location Map

Incident Narrative

THE TW CORONA COMPRESSOR STATION 8 - SIX INCH DISCHARGE BLOWDOWN VALVE OPENED UNINTENTIONALLY AND BLEW GAS TO THE ATMOSPHERE. THE BLOW DOWN VALVE, SHAFER OPERATOR PILOT GAS LINE FROZE OFF, DUE TO SUB ZERO TEMPERATURES CAUSING A LOSS OF PILOT PRESSURE, WHICH HOLDS THE VALVE IN THE CLOSED POSITION.