ENLINK LBU-GAS&LIQUIDS

gas_transmission Incident — — March 4, 2019

Incident Information

Incident DateMarch 4, 2019
OperatorENLINK LBU-GAS&LIQUIDS
CommodityNATURAL GAS
Pipeline Typegas_transmission

Location

State
Coordinates32.00766, -93.72673

Cause

CauseCORROSION FAILURE
SubcauseEXTERNAL CORROSION

Casualties

Fatalities0
Injuries0

Costs

Property Damage$131,536
Emergency Response$0
Other Costs$0

Location Map

Incident Narrative

DURING THE ANNUAL CP SURVEY, OPERATIONS PERSONNEL FOUND AN APPARENT SMALL LEAK INSIDE A CASING AT A RAILROAD CROSSING. THE LEL ON THE VENT PIPE WAS FOUND TO BE 15%. IF THE REPAIR COST DID NOT EXCEED THE $50,000 THRESHOLD, THIS INCIDENT WOULD NOT HAVE BEEN REPORTABLE. THE ACTUAL LEAK WAS A MINOR PIN HOLE INSIDE THE CASING. IT APPEARS THE COATING WAS DAMAGED DURING THE INITIAL INSTALLATION OF THE CROSSING. THE CASING WAS NOT SHORTED. THE ESTIMATED GAS LOSS IS <1MCF.