TENNESSEE GAS PIPELINE COMPANY

gas_transmission Incident — — January 22, 2025

Incident Information

Incident DateJanuary 22, 2025
OperatorTENNESSEE GAS PIPELINE COMPANY
CommodityNATURAL GAS
Pipeline Typegas_transmission

Location

State
Coordinates29.53872, -96.13220

Cause

CauseMATERIAL FAILURE OF PIPE OR WELD
Subcause"DESIGN-, CONSTRUCTION-, INSTALLATION-, OR FABRICATION-RELATED"

Casualties

Fatalities0
Injuries0

Costs

Property Damage$300,000
Emergency Response$2,534
Other Costs$0

Location Map

Incident Narrative

"AT APPROXIMATELY 12:35 P.M. CENTRAL TIME, TENNESSEE GAS PIPELINE (TGP) 100-3 EXPERIENCED A PIPELINE FAILURE RESULTING IN A FIRE IN EAST BERNARD, TEXAS. THE IMPACTED PIPELINE SEGMENT WAS ISOLATED AND SHUT DOWN. EMERGENCY RESPONDERS WERE ON SITE. REPAIRS HAVE BEEN MADE TO REPLACE THE AFFECTED PIPE. THROUGH METALLURGICAL ANALYSIS, TGP CONCLUDED THAT THE FAILURE OCCURRED FROM SEPARATION OF A JOINT GIRTH WELD CAUSED BY INCOMPLETE PENETRATION OF THE THE GIRTH WELD."

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in