KINDER MORGAN TEXAS PIPELINE CO

gas_transmission Incident — — April 28, 2025

Incident Information

Incident DateApril 28, 2025
OperatorKINDER MORGAN TEXAS PIPELINE CO
CommodityNATURAL GAS
Pipeline Typegas_transmission

Location

State
Coordinates31.11957, -101.56785

Cause

CauseEQUIPMENT FAILURE
SubcauseMALFUNCTION OF CONTROL/RELIEF EQUIPMENT

Casualties

Fatalities0
Injuries0

Costs

Property Damage$2,133
Emergency Response$0
Other Costs$0

Location Map

Incident Narrative

"BIG LAKE UNIT#1 HAD A FAILED POWER SUPPLY CAUSING A COMMUNICATION FAILURE. THE LOST COMMUNICATION AND TRIPPED THE SUCTION ALARM. THE UNIT VENT VALVE IS A FAIL OPEN TYPE. THE VENT VALVE OPENED; HOWEVER, THE SUCTION AND DISCHARGE VALVES ARE CONTROLLED BY THE TURBINE UNIT PLC. THE VALVES ARE A FAIL IN LAST STATE, SO THAT WITHOUT POWER WHEN THEY FAILED OPEN CAUSING A RELEASE OF NATURAL GAS. 9/17/2025: UPDATED COUNTY AND DAYLIGHT SAVINGS TIME AS PER PHMSA'S REQUEST."