DTE GAS COMPANY

gas_transmission Incident — — May 14, 2025

Incident Information

Incident DateMay 14, 2025
OperatorDTE GAS COMPANY
CommodityNATURAL GAS
Pipeline Typegas_transmission

Location

State
Coordinates44.26426, -84.23519

Cause

CauseCORROSION FAILURE
SubcauseEXTERNAL CORROSION

Casualties

Fatalities0
Injuries0

Costs

Property Damage$208,527
Emergency Response$0
Other Costs$0

Location Map

Incident Narrative

"5/14/25: WHILE HAND SCRAPING FOR MAINTENANCE DURING PRIOR DEFECT IDENTIFIED DURING IN-LINE-INSPECTION, A LEAK DEVELOPED ON THE ALPENA 16"" TRANSMISSION LINE. PIPELINE IS ODORIZED 16"" COATED STEEL X52 0.250 WALL THICKNESS, INSTALLED IN 1964, CURRENT MAOP 812 PSIG, NORMAL OPERATING 670 PSIG, PRESSURE REDUCED TO 480 PSIG PRIOR TO MAINTENANCE EXCAVATION. (ORIGINAL MAOP WAS 869 PSIG, DERATED IN 2017 TO 812 PSIG.) AFTER LEAK DEVELOPED, PIPELINE WAS BLOWN DOWN TO ZERO PRESSURE AND CUTOUT WAS MADE. ON 5/22/25 REPAIR WAS COMPLETED AND PIPELINE WAS THEREAFTER RETURNED TO SERVICE. ON 6/11/25, CONTRACTOR REPAIR COSTS EXCEEDED PHMSA REPORTING THRESHOLD AND THE INCIDENT WAS REPORTED TO PHMSA/NRC AT 2:39PM ON THE SAME DAY (NRC # 1433791)."