"MOUNTAINWEST PIPELINE, LLC"

gas_transmission Incident — — June 6, 2025

Incident Information

Incident DateJune 6, 2025
Operator"MOUNTAINWEST PIPELINE, LLC"
CommodityNATURAL GAS
Pipeline Typegas_transmission

Location

State
Coordinates40.99583, -109.21250

Cause

CauseEQUIPMENT FAILURE
SubcauseCOMPRESSOR OR COMPRESSOR-RELATED EQUIPMENT

Casualties

Fatalities0
Injuries0

Costs

Property Damage$750,000
Emergency Response$0
Other Costs$0

Location Map

Incident Narrative

"ON JUNE 6TH 2025 12:11PM MST CLAY BASIN CS UNIT 1 AUTOMATICALLY SHUTDOWN DUE TO SIMULTANEOUS HIGH TURBO VIBRATION AND ENGINE VIBRATION ALARMS. APPROXIMATELY 32 SECONDS LATER, GAS WAS DETECTED IN THE BUILDING, TRIGGERING AN EMERGENCY SHUTDOWN (ESD) OF THE ENTIRE STATION. ONE FIELD PERSONNEL WAS PRESENT IN THE COMPRESSOR BUILDING, BUT NOT IN THE VICINITY OF THE FAILURE. THE UNIT 1 COMPRESSOR CROSSHEAD SHOE SEPARATED FROM THE CROSSHEAD AND WAS JAMMED INTO THE CROSSHEAD CAUSING THE FRAME TO BREAK. THE COMPRESSOR ROD WAS BENT AS A PART OF THE FAILURE DESTROYING THE GAS PACKING CAUSING A GAS RELEASE TO OCCUR. INCIDENT INVESTIGATION IS ONGOING. PRELIMINARY INDICATIONS POINTS TOWARDS CONTRIBUTING FACTOR OF A BOLT AND STUD FAILURE THAT CAUSED THE SHOE TO BE LOOSE. ACTION TAKEN DURING THE INTERIM OF THE INVESTIGATION WAS ALL OTHER UNITS AT KASTLER CS WERE INSPECTED TO ENSURE ALL CROSSHEAD NUTS HAD NOT BEEN LOOSENED."

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in