NORTHERN NATURAL GAS CO

gas_transmission Incident — — November 2, 2025

Incident Information

Incident DateNovember 2, 2025
OperatorNORTHERN NATURAL GAS CO
CommodityNATURAL GAS
Pipeline Typegas_transmission

Location

State
Coordinates42.04555, -94.04541

Cause

CauseEQUIPMENT FAILURE
SubcauseMALFUNCTION OF CONTROL/RELIEF EQUIPMENT

Casualties

Fatalities0
Injuries0

Costs

Property Damage$100
Emergency Response$450
Other Costs$0

Location Map

Incident Narrative

"ON NOVEMBER 2, 2025, AT 1712 HOURS, A SENIOR PIPELINE TECHNICIAN, FOR THE OGDEN, IOWA, PLANT TEAM, HEARD A RELIEF VALVE VENTING FROM HIS HOME NEAR THE OGDEN, IOWA, COMPRESSOR STATION AND ALERTED THE ON-CALL TECHNICIAN. THE TECHNICIAN ARRIVED TO FIND COMPRESSOR UNIT 18 RELIEF VALVE VENTING GAS. THE RELIEF VALVE WAS ACTIVATED DUE TO BROKEN TUBING THAT CAUSED THE DOME PRESSURE OF THE RELIEF VALVE TO GO TO ZERO PSIG. ADDITIONAL HORSEPOWER WAS STARTED TO ENSURE THROUGHPUT WAS MET. AT 1755 HOURS, COMPRESSOR UNIT 18 WAS ISOLATED, SHUT DOWN AND BLOWN DOWN. ONCE THE UNIT WAS BLOWN DOWN REPAIRS WERE MADE TO THE BROKEN TUBING, AND THE COMPRESSOR UNIT WAS PURGED AND MADE READY FOR SERVICE. DURING THE INVESTIGATION IT WAS NOTED THAT EXCESSIVE VIBRATION AND INSUFFICIENT SUPPORT MAY HAVE CONTRIBUTED TO THE TUBING FAILURE. SUPPORT HAS BEEN ADDED TO THE DEVICE TO RECTIFY THE VIBRATION CONCERN."