SOUTHERN NATURAL GAS CO

gas_transmission Incident, , January 29, 2026

Incident Information

Incident DateJanuary 29, 2026
OperatorSOUTHERN NATURAL GAS CO
CommodityNATURAL GAS
Pipeline Typegas_transmission

Location

State
Coordinates29.72740, -91.41710

Cause

CauseEQUIPMENT FAILURE
SubcauseMALFUNCTION OF CONTROL/RELIEF EQUIPMENT

Casualties

Fatalities0
Injuries0

Costs

Property Damage$0
Emergency Response$100
Other Costs$0

Location Map

Incident Narrative

"FUEL GAS REGULATOR ON SHADYSIDE UNIT #1 LEAKED AND RELEASED GAS INTO THE BUILDING ENGINE ROOM BASEMENT. THIS CAUSED THE ACTIVATION OF THE C/S GAS DETECTION SYSTEM, WHICH RESULTED IN THE EMERGENCY STOPPING OF ALL ENGINES AND THE BLOWDOWN OF THEIR ASSOCIATED COMPRESSORS AND THE STATION FUEL GAS PIPING. THE 15-MINUTE ESD ROLLOVER TIMER EXPIRED DUE TO THE ENGINE ROOM FAILING TO VENT COMPLETELY IN CONJUNCTION WITH THE C/S GAS DETECTION SYSTEM STILL BEING IN ALARM. ESD BLOCK VALVES #106 AND #49 FAILED TO FULLY CLOSE WHICH RESULTED IN GAS TO CONTINUE TO VENT UNTIL THE STATION COULD BE ISOLATED BY OPERATIONS PERSONNEL. THE AMOUNT OF GAS RELEASED WAS 20.324 MMCF. THIS RELEASE WAS REPORTED TO THE LOUISIANA STATE POLICE AND THE NRC. NO INJURIES. NO PROPERTY DAMAGE."