PECO ENERGY CO

gas_distribution Incident — BROOKHAVEN, PA — April 25, 2011

Incident Information

Incident DateApril 25, 2011
OperatorPECO ENERGY CO
CommodityNATURAL GAS
Pipeline Typegas_distribution

Location

CityBROOKHAVEN
StatePA
CountyDELAWARE
Coordinates39.85474, -75.39189

Cause

CauseINCORRECT OPERATION
SubcauseDAMAGE BY OPERATOR OR OPERATOR'S CONTRACTOR NOT RELATED TO EXCAVATION AND NOT DUE TO MOTORIZED VEHICLE/EQUIPMENT DAMAGE

Casualties

Fatalities0
Injuries1

Costs

Property Damage$0
Emergency Response$0
Other Costs$0

Location Map

Incident Narrative

"ON APRIL 25, 2011, A PECO GAS CONSTRUCTION AND MAINTENANCE CREW WAS REPAIRING A LEVEL ONE LEAK. WHILE CUTTING-OUT THE LEAKING PORTION OF A SERVICE PIPE WITH A BATTERY POWERED SAW, NATURAL GAS IGNITED. IMMEDIATELY, THE FIRE WAS EXTINGUISHED AND THE FLOW OF GAS WAS STOPPED. A CREW MEMBER RECEIVED MINOR BURNS TO HIS FACE. EMPLOYEE SHOULD HAVE VERIFIED THE SERVICE WAS PROPERLY PURGED OUT OF SERVICE PRIOR TO USING THE BATTERY POWERED SAW OR A MANUAL PIPE CUTTER COULD HAVE ALSO BEEN USED TO ELIMINATE THE SOURCE OF IGNITION."

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.