Kidde 10 lb. industrial dry chemical fire extinguishers with black plastic Zytel® nylon valves in...

CPSC Recall #05-589 — July 25, 2005

Recall #05-589 Date: July 25, 2005 Remedy: New Instructions

Product

Kidde 10 lb. industrial dry chemical fire extinguishers with black plastic Zytel® nylon valves in steel cylinders manufactured between 1991 and 2000

Description

This Alert involves all Kidde 10 lb. dry chemical fire extinguishers manufactured with a black plastic Zytel® nylon valve assembly and a steel cylinder between 1991 and 2000. These units were the subject of Kidde Service Bulletin 007 issued on July 21, 2004. These units were designed for commercial and industrial applications, and the majority of these units were placed into service in factories, plants, businesses and other commercial locations as they require service by a qualified Fire Extinguisher Distributor or Service Organization every 6 years. Some of these units are in use in residential settings. The affected extinguishers have a steel cylinder with a welded neck ring and are between 19 to 21 inches tall as depicted in the image below. This Alert does not apply to Kidde's smaller 2 1/2 and 5 lb. residential fire extinguishers.

Hazard

The nylon valves on these extinguishers can separate from the steel cylinder during the 6-year recharge service or shortly afterwards creating a safety hazard to fire extinguisher service personnel and consumers.

Incidents / Injuries

Kidde has received five reports of valve separation during either technical service of the units or shortly afterwards, resulting in three reports of injuries.

Remedy

Fire Extinguisher Distributors and Service Organizations must immediately stop servicing all units covered under this Alert. Kidde has instituted a Fire Extinguisher Replacement Program ("Replacement Program") for all units covered by this Alert. If you are a Fire Extinguisher Distributor or Service Organization and you have not already received a copy of the Replacement Program, as outlined in Service Bulletin 007, please contact the number below. Only professional Fire Extinguisher Distributors and Service Organizations should remove the affected units and the steps as outlined in the Replacement Program must be followed. 

Units Affected

About 470,000

Sold At

Commercial fire equipment distributors and stores nationwide between 1991 and 2000.

Manufacturer

Walter Kidde Portable Equipment Inc., of Mebane, N.C.

Manufactured In

United States