BARTS ELECTRIC

Direct exposure to electricity, unspecified — Electrical burns, unspecified — LENEXA, KANSAS

HOSPITALIZED — Worker hospitalized after incident at BARTS ELECTRIC in LENEXA, KANSAS
Employer BARTS ELECTRIC Report ID 2019077671
Address 107th & Lackman Road City, State ZIP LENEXA, KANSAS 66215
Event Date July 26, 2019 Outcome Hospitalized
Nature of Injury Electrical burns, unspecified Body Part Multiple body parts, n.e.c.
Event Type Direct exposure to electricity, unspecified Source of Injury Switchboards, switches, fuses
Industry (NAICS) 238210 Inspection #
GPS Coordinates 41.69000, -87.60000

Incident Narrative

An employee had a team working on a new conduit feeder to a substation switchgear. The 480-volt side of the switchgear where the work was taking place was locked out, tagged out, and verified with a meter to not have power. At the entrance point of the conduit into the substation, another employee was using a knock-out set to punch a hole into the gear. He was having trouble getting the knock-out started, so the injured employee attempted to help him. The injured employee was standing on a two-step riser working with his hands over his head. He was trying to adjust and move some existing wires out of the location of the new knock-out location to thread on the cutting die. As he was moving and pulling, he pushed against the side wall of the switchgear. The side wall flexed into the adjacent compartment, touching a buss that caused an arc flash. The injured employee suffered burns to the hands, left arm, and midsection of his body.

Incident Summary

On July 26, 2019, a worker at BARTS ELECTRIC in LENEXA, KANSAS suffered electrical burns, unspecified to the multiple body parts, n.e.c.. The incident was classified as direct exposure to electricity, unspecified, with switchboards, switches, fuses identified as the source of injury. The worker was hospitalized.

Context

OSHA has recorded 730 severe injury reports involving "Direct exposure to electricity, unspecified" incidents in our database. Browse all Direct exposure to electricity, unspecified injuries.

See all reports for BARTS ELECTRIC.

Similar Incidents

Other severe injury reports involving Direct exposure to electricity, unspecified events:

Date Employer Location Nature Outcome
Jul 21, 2022 McKinley Companies, LLC ORLANDO, FLORIDA Second degree electrical burns Hosp.
Jul 25, 2018 Smart Building Technologies WASHINGTON, DISTRICT OF COLUMBIA Electrical burns, unspecified Hosp.
May 18, 2023 HCL Contracting LLC CALVERT, ALABAMA Electrical burns, unspecified Hosp.
Feb 20, 2021 J & J Oilfield Electric Co., Inc. BRECKENRIDGE, TEXAS Third or fourth degree electrical burns Hosp.
Jul 17, 2019 CWP Asset Corporate KATY, TEXAS Electrical burns, unspecified Hosp.
Nov 4, 2017 Sun Industrial Group, LLC BRUSLY, LOUISIANA Electrical burns, unspecified Hosp.
Jun 5, 2015 Dixie Electric DENVER CITY, TEXAS Electrical burns, unspecified Hosp.
Jun 2, 2021 Portage Plastics Corporation PORTAGE, WISCONSIN Amputations Amp.

About This OSHA Report

This is a severe injury report filed with OSHA. Employers are required to report all work-related fatalities and severe injuries within 8 to 24 hours. Browse more reports by industry or state below.

Browse All Injury Reports