DCP MIDSTREAM

hazardous_liquid Incident — — October 3, 2014

Incident Information

Incident DateOctober 3, 2014
OperatorDCP MIDSTREAM
CommodityHVL OR OTHER FLAMMABLE OR TOXIC FLUID WHICH IS A GAS AT AMBI
Pipeline Typehazardous_liquid

Location

State
Coordinates29.08966, -96.62664

Cause

CauseNATURAL FORCE DAMAGE
SubcauseLIGHTNING

Casualties

Fatalities0
Injuries0

Costs

Property Damage$0
Emergency Response$0
Other Costs$0

Location Map

Incident Narrative

"AT APPROXIMATELY 2:15 AM, AT DCP MIDSTREAM WILBREEZE PUMP STATION LOCATED NEAR EDNA, TX, THE SHUTDOWN VALVE ESD120 INADVERTENTLY WENT CLOSED CAUSING A THERMAL RELIEF VALVE TO LIFT AND VENT APPROXIMATELY 34.6 BARRELS OF NGL TO ATMOSPHERE. THE OPERATOR AT THE HOUSTON CONTROL CENTER CALLED AN NGL TECHNICIAN AT APPROXIMATELY 2:30 AM TO INVESTIGATE. THE NGL TECHNICIAN ARRIVED AT THE SITE AT 3:20 AM AND BEGAN TO INVESTIGATE THE CLOSURE AND RETURNED THE VALVE TO THE OPEN POSITION. AT APPROXIMATELY 3:30 AM, THE TECHNICIAN SAW A FLAME ON TOP OF THE VENT STACK. IT IS PRESUMED THAT STATIC ELECTRICITY OR A LIGHTNING STRIKE FROM A STORM IN THE AREA IGNITED THE NGL VAPORS ON TOP OF THE VENT STACK. THE TECHNICIAN THEN NOTIFIED THE OPERATIONS SUPERVISOR AT APPROXIMATELY 4:01AM. THE INVESTIGATION DETERMINED THAT ESD120 INADVERTENTLY CLOSED DUE TO A TRANSIENT VOLTAGE SPIKE/DIP FROM THE BAD WEATHER."

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in