EXXONMOBIL OIL CORPORATION-TERMINALS

hazardous_liquid Incident — — October 14, 2013

Incident Information

Incident DateOctober 14, 2013
OperatorEXXONMOBIL OIL CORPORATION-TERMINALS
CommodityREFINED AND/OR PETROLEUM PRODUCT (NON-HVL) WHICH IS A LIQUID
Pipeline Typehazardous_liquid

Location

State
Coordinates33.86657, -117.83862

Cause

CauseINCORRECT OPERATION
SubcauseTANK, VESSEL, OR SUMP/SEPARATOR ALLOWED OR CAUSED TO OVERFILL OR OVERFLOW

Casualties

Fatalities0
Injuries0

Costs

Property Damage$0
Emergency Response$30,000
Other Costs$0

Location Map

Incident Narrative

THE EXXONMOBIL ATWOOD TERMINAL WAS RECEIVING GASOLINE/WATER MIXTURE FROM M-3 HYDROTEST INTO TANK 14. TANK LEVEL WAS BEING MONITORED BY TERMINAL PERSONNEL FOR SAFE LEVEL SHUT DOWN OF 42FT. AT 13:20, WITH THE TANK LEVEL SHOWING ~41, THE TANK BEGAN TO OVERFILL OUT OF THE THREE LOWER TANK VENTS IN TO SECONDARY CONTAINMENT. EMERGENCY OVERFILL PROTECTION DID NOT ACTIVATE. THE INCOMING PIPELINE WAS SHUT DOWN VIA EMERGENCY SHUT DOWN AND SYSTEM WAS ISOLATED AT THE ATWOOD METER STATION (VALVES #1 & #3 AND MOV #14). ROOT CAUSE OF INCIDENT THE ATWOOD TANK 14 AUTOMATIC TANK GAUGING SYSTEM UTILIZES TWO PRESSURE TRANSMITTERS TO CALCULATE MASS AND DENSITY AND CALCULATES A TANK LEVEL BASED ON THE TANK DIMENSIONS. BECAUSE THE PRESSURE TRANSMITTERS ARE LOCATED AT A FIXED DISTANCE AT THE BOTTOM OF THE TANK, THE SYSTEM DOES NOT HAVE THE CAPABILITY OF ACCURATELY CALCULATING TANK LEVELS WHEN THERE IS STRATIFICATION OF DIFFERENT DENSITY LIQUIDS SUCH AS GASOLINE AND WATER. THIS IS THE DIRECT CAUSE OF THE INACCURATE TANK LEVELS THAT LED TO THE OVERFILLING OF THE TANK.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in