DCP MIDSTREAM

hazardous_liquid Incident —

Incident Information

Report Date
OperatorDCP MIDSTREAM
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates31.83244, -104.24799

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

THE HIDALGO PLANT, WHICH DELIVERS TO THE DCP HIDALGO METER STATION, STARTED THEIR NGL PUMPS BUT BROUGHT THEM ON TOO FAST. THIS CREATED AN ABNORMALLY HIGH OPERATING CONDITION THAT SHOULD HAVE TRIPPED MOV-100 (ESD VALVE) TO CLOSE ON THE INLET TO OUR HIDALGO NGL METER STATION. THE MOV-100 VALVE FAILED TO CLOSE WHEN IT RECEIVED A HIGH PRESSURE SHUTDOWN OF 1285 PSIG DUE TO A HYDRAULIC NEEDLE VALVE THAT WAS SHUT AND/OR A BAD SOLENOID VALVE. MITIGATIVE ACTIONS INCLUDE RETESTING, REBUILDING AND REINSTALLING PSV 200; REPLACING THE SOLENOID VALVE AND TIGHTEN THE PACKING GLAND ON THE VALVE STEM OF THE HYDRAULIC NEEDLE VALVE