PLAINS PIPELINE, L.P.

hazardous_liquid Incident —

Incident Information

Report Date
OperatorPLAINS PIPELINE, L.P.
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates28.52601, -99.22348

Cause

CauseCORROSION FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

APPROXIMATELY 20 BBLS OF CRUDE OIL WERE RELEASED FROM DEAD LEG PIPING NEAR THE EAGLE FORD II BOOSTER PUMP SUCTION MANIFOLD OF PLAINS GARDENDALE JV TERMINAL AS A RESULT OF INTERNAL CORROSION. THE CAUSE OF CORROSION HAS YET TO BE DETERMINED. A SUPPLEMENTAL REPORT WILL BE SUBMITTED UPON DETERMINATION OF THE ROOT CAUSE. THE NATIONAL RESPONSE CENTER (NRC) WAS NOTIFIED UPON ESTIMATED COSTS EXCEEDING THE $50,000 THRESHOLD AND ASSIGNED REPORT #1175583. SUPPLEMENTAL NARRATIVE: THE RESULTS OF THE METALLURGICAL ANALYSIS INDICATE THE INTERNAL CORROSION WAS CAUSED BY PRODUCED WATER CONTAINING A MIXTURE OF SALTS, OXYGEN AND CARBON DIOXIDE, WITH MIC BEING A CONTRIBUTING FACTOR. PLAINS HAS COMPLETED NDT INSPECTIONS AT THE GARDENDALE JV FACILITY SINCE THIS INCIDENT, WHICH INCLUDED THE MANIFOLD, IN ORDER TO CORRECT ANY ADDITIONAL ANOMALIES, AND THUS PREVENTING RECURRENCE.