TARGA DOWNSTREAM LLC

hazardous_liquid Incident —

Incident Information

Report Date
OperatorTARGA DOWNSTREAM LLC
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates31.59637, -96.10478

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

0300: EMPLOYEE CALLED TO SITE TO INVESTIGATE HIGH SEAL PRESSURE ALARM. 0345: EMPLOYEE ARRIVED ON SITE AND FOUND PRV ON PUMP DISCHARGE RELIEVING TO FLARE HEADER. PRV IMMEDIATELY BLOCKED IN. 0415: FLARE SUBSIDED, AND PRESSURE DROPPED. 0624: FLARE PRESSURE BEGAN TO RISE AGAIN DUE TO ANOTHER PRV LIFTING. PRV SHUT IN, SIMULTANEOUS TO FLARE KNOCK-OUT OVERFILLING, SPILLING AND IGNITING. 0630: PUMP STATION WAS SHUT DOWN (PRODUCT BYPASSED). ONCE PRODUCT WAS SHUT IN, FIRE SUBSIDED. NOTE: PRV'S ARE USED AS THERMAL RELIEF ONLY. CORRECTIVE ACTIONS INCLUDE INSTALLATION OF POPPET VALVES (INSTEAD OF PRV'S) THAT ALLOW A FLOW OF HIGHER PRESSURE TO A LOWER PRESSURE POINT WITHIN THE STATION. PRODUCT STAYS IN THE PIPE, REDUCING LIKELIHOOD OF RECURRENCE. POPPET VALVES WERE INSTALLED, TESTED AND OPERATIONAL WITHIN ONE WEEK OF ACCIDENT.