BUCKEYE PARTNERS, LP

hazardous_liquid Incident —

Incident Information

Report Date
OperatorBUCKEYE PARTNERS, LP
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates42.24180, -83.31918

Cause

CauseINCORRECT OPERATION
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

ON JANUARY 21ST, 2017, A BUCKEYE EMPLOYEE WORKING AT THE DETROIT METRO TERMINAL DISCOVERED JET FUEL LEAKING FROM AN OBSERVATION CANISTER USED FOR M&QC. THE EMPLOYEE CLOSED THE VALVE TO STOP THE FLOW OF JET FUEL INTO THE CANISTER. ALL INTERNAL AND EXTERNAL NOTIFICATIONS WERE COMPLETED. THE FUEL FILLED UP THE CONCRETE CONTAINMENT AREA AND MIGRATED TO THE CONTAINMENT DIKE, NONE OF WHICH MIGRATED OFF SITE. OSRO ARRIVED ON SITE AND CLEANED THE AREA BEFORE DETERMINING TO BE SAFE. THE CHECK VALVES THAT FAILED, CAUSING THE RELEASE, ARE UNDER INVESTIGATION TO DETERMINE THE CAUSE. 3/8/2017 THE RELEASE INVESTIGATION DETERMINED THE ROOT CAUSE OF THIS SPILL TO BE HUMAN ERROR. THE BUCKEYE EMPLOYEE OPERATING THE STATION AT THE TIME FAILED TO FOLLOW PROCEDURES AND LEFT THE FACILITY WITHOUT VERIFYING VALVE ALIGNMENT AFTER CHECKING FOR WATER IN THE JET FILTERS. THIS OPERATIONAL ERROR EXPOSED TWO CHECK VALVES TO TANK HEAD PRESSURE WHEN THE FACILITY SHUT DOWN. THE CHECK VALVES DID NOT PERFORM AS DESIGNED AND ALLOWED JET FUEL TO LEAK PAST THEM FILLING THE INSPECTION POT AND ULTIMATELY OVERFLOWING OUT OF THE TOP OF THE POT.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in