PHILLIPS 66 PIPELINE LLC
hazardous_liquid Incident —
Incident Information
| Report Date | — |
| Operator | PHILLIPS 66 PIPELINE LLC |
| Commodity | — |
| Pipeline Type | hazardous_liquid |
Location
| State | |
| Coordinates | 35.41208, -119.72993 |
Cause
| Cause | CORROSION FAILURE |
| Subcause | — |
Casualties
| Fatalities | 0 |
| Injuries | 0 |
Costs
| Property Damage | — |
| Lost Commodity | — |
| Public/Private Damage | — |
| Emergency Response | — |
| Environmental Remediation | — |
| Other Costs | — |
Location Map
Incident Narrative
LOCAL OPERATIONS RECEIVED A CALL FROM A PRODUCTION COMPANY OF A POSSIBLE RELEASE OF CRUDE FROM A CONNECTION POINT. UPON ARRIVAL AT THE SCENE A PINHOLE LEAK AT THE 6:00 POSITION WAS FOUND IN ABOVE GROUND PIPING. UPDATE REQUESTED FROM ACCIDENT TEAM: D-2: 48 ROLL OFF BINS OF IMPACTED SOIL WERE SENT TO BE REMEDIATED AND THE REMOVED SOIL AREA WAS REPLACED WITH ROAD BASE. E-6&9: THE LEAK RATE WAS BELIEVED TO BE IN THE 1.5 TO 2 BPH LEAK RANGE. AVERAGE FLOW RATE ON THIS NC15 SYSTEM WAS APPROXIMATELY 1100 BPH FOR MOST OF JANUARY. THE LEAK RATE WAS <0.2% OF FLOW. CPM LEAK DETECTION SYSTEMS LIKE OUR PLM SYSTEM TYPICALLY AREN'T EFFECTIVE FOR IDENTIFYING SMALL LEAKS BELOW 0.5% (DUE TO EQUIPMENT ACCURACIES AND OPERATIONAL CONSIDERATIONS). THE CONTROLLER DID NOT RECEIVE ANY ALARMS RELATED TO THIS EVENT FROM PLM OR OTHERWISE. G1-8: THE CSFM PERFORMED A FIELD EXAMINATION AND INSTRUCTED US THERE WAS NO NEED FOR A METALLURGICAL ANALYSIS. G1-10, 13, &18: THE RELEASE OCCURRED IN AN UNDERUTILIZED PIECE OF MANIFOLD PIPING THAT HAS SINCE BEEN REMOVED FROM THE MANIFOLD TO PREVENT ANY REOCCURRENCE. THIS AREA WAS AN UNDERUTILIZED PORTION OF MANIFOLD PIPING THAT HAD NOT SEEN ANY FLOW FOR A LONG PERIOD OF TIME IS WHAT IS BELIEVED TO HAVE CAUSED THIS INCIDENT.
About This Pipeline Incident
Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.