KINDER MORGAN TEXAS PIPELINE CO

gas_transmission Incident — — February 7, 2025

Incident Information

Incident DateFebruary 7, 2025
OperatorKINDER MORGAN TEXAS PIPELINE CO
CommodityNATURAL GAS
Pipeline Typegas_transmission

Location

State
Coordinates28.65236, -97.90191

Cause

CauseEQUIPMENT FAILURE
SubcauseNON-THREADED CONNECTION FAILURE

Casualties

Fatalities0
Injuries0

Costs

Property Damage$14,900,000
Emergency Response$100
Other Costs$0

Location Map

Incident Narrative

"ON FEBRUARY 7, 2025 AT 21:45, KM PERSONNEL ARRIVED ON SITE AT KENEDY COMPRESSOR STATION TO FIND THE COMPRESSOR BUILDING ON FIRE. AN INTERNAL INVESTIGATION FOUND THAT THE FIRE ORIGINATED FROM AN OIL LEAK ON THE SUCTION SIDE OF THE COMPRESSOR. A FAILED GASKET ON THE LUBE OIL DRAIN LINE CAUSED THE DRAIN LINE TO DISCONNECT AND FALL OUT OF PLACE. THE LEAKING OIL THEN CAME INTO CONTACT WITH THE HOT SURFACE OF THE EXHAUST COLLECTOR, WHERE IT IGNITED. ALL INTERNAL AND EXTERNAL NOTIFICATIONS WERE MADE AS REQUIRED."